3  Functions  Issue 07/04 
  MICROMASTER 420    Operating Instructions 
74  6SE6400-5AA00-0BP0  
3.5.5.4  Digital output (DOUT) 
 
P0731 =... 
 
 
BI: Function of digital output 1* 
Defines source of digital output 1. 
P0748 = 0
 
Invert digital output 
Defines high and low states of relay for a 
given function. 
Common Settings: 
52.0 Drive ready  0  Closed 
52.1 Drive ready to run  0  Closed 
52.2  Drive running  0  Closed 
52.3  Drive fault active  0  Closed 
52.4  OFF2 active  1  Closed 
52.5  OFF3 active  1  Closed 
52.6  Switch on inhibit active  0  Closed 
52.7  Drive warning active  0  Closed
 
 
-1
0
1
Invert DOUTs
0 ... 1
P0748 (0)
CO/BO: State DOUTs
r0747
r0747
Kl.10
Kl.11
.0
DOUT channel
NO
COM
(52:3)
BI: Fct. of DOUT 1
P0731
 
3.5.5.5  Selection of frequency setpoint 
 
P1000 =... 
 
 
Selection of frequency setpoint 
 0  No main setpoint 
 1  MOP setpoint 
 2  Analog setpoint 
 3  Fixed frequency 
  4  USS on BOP link 
  5  USS on COM link 
  6  CB on COM link 
 
MOP
ADC
FF
USS
BOP link
USS
COM link
CB
COM link
P1000 = 12
P1000 = 12
Sequence control
Additonal
setpoint
Main
setpoint
Setpoint
channel
Motor
control
 
 
52.3 
0 
2