3.5.5.4 Digital output (DOUT)
P0731 =...
BI: Function of digital output 1*
Defines source of digital output 1.
P0748 = 0
Invert digital output
Defines high and low states of relay for a
given function.
Common Settings:
52.0 Drive ready 0 Closed
52.1 Drive ready to run 0 Closed
52.2 Drive running 0 Closed
52.3 Drive fault active 0 Closed
52.4 OFF2 active 1 Closed
52.5 OFF3 active 1 Closed
52.6 Switch on inhibit active 0 Closed
52.7 Drive warning active 0 Closed
-1
0
1
Invert DOUTs
0 ... 1
P0748 (0)
CO/BO: State DOUTs
r0747
r0747
Kl.10
Kl.11
.0
DOUT channel
NO
COM
(52:3)
BI: Fct. of DOUT 1
P0731
3.5.5.5 Selection of frequency setpoint
P1000 =...
Selection of frequency setpoint
0 No main setpoint
1 MOP setpoint
2 Analog setpoint
3 Fixed frequency
4 USS on BOP link
5 USS on COM link
6 CB on COM link
MOP
ADC
FF
USS
BOP link
USS
COM link
CB
COM link
P1000 = 12
P1000 = 12
Sequence control
Additonal
setpoint
Main
setpoint
Setpoint