3  Functions  Issue 07/04 
  MICROMASTER 420    Operating Instructions 
118  6SE6400-5AA00-0BP0  
Table 3-21  Possible parameter settings for P0719 
Value  Command source  Setpoint source 
0  Cmd = BICO parameter  Setpoint = BICO parameter 
1  Cmd = BICO parameter  Setpoint = MOP setpoint 
2  Cmd = BICO parameter  Setpoint = Analog setpoint 
3  Cmd = BICO parameter  Setpoint = Fixed frequency 
4  Cmd = BICO parameter  Setpoint = USS on BOP link 
5  Cmd = BICO parameter  Setpoint = USS on COM link 
6  Cmd = BICO parameter  Setpoint = CB on COM link 
10  Cmd = BOP  Setpoint = BICO parameter 
11  Cmd = BOP  Setpoint = MOP setpoint 
12  Cmd = BOP  Setpoint = Analog setpoint 
13  Cmd = BOP  Setpoint = Fixed frequency 
15  Cmd = BOP  Setpoint = USS  on BOP link 
16  Cmd = BOP  Setpoint = USS  on COM link 
40  Cmd = USS on BOP link  Setpoint = BICO parameter 
41  Cmd = USS on BOP link  Setpoint = MOP setpoint 
42  Cmd = USS on BOP link  Setpoint = Analog setpoint 
43  Cmd = USS on BOP link  Setpoint = Fixed frequency. 
44  Cmd = USS on BOP link  Setpoint = USS  on BOP link 
45  Cmd = USS on BOP link  Setpoint = USS  on COM link 
46  Cmd = USS on BOP link  Setpoint = CB on COM link 
50  Cmd = USS on COM link  Setpoint = BICO parameter 
51  Cmd = USS on COM link  Setpoint = MOP setpoint 
52  Cmd = USS on COM link  Setpoint = Analog setpoint 
53  Cmd = USS on COM link  Setpoint = Fixed frequency 
54  Cmd = USS on COM link  Setpoint = USS  on BOP link 
55  Cmd = USS on COM link  Setpoint = USS  on COM link 
60  Cmd = CB on COM link  Setpoint = BICO parameter 
61  Cmd = CB on COM link  Setpoint = MOP setpoint 
62  Cmd = CB on COM link  Setpoint = Analog setpoint 
63  Cmd = CB on COM link  Setpoint = Fixed frequency 
64  Cmd = CB on COM link  Setpoint = USS  on BOP link 
66  Cmd = CB on COM link  Setpoint = USS  on COM link