3  Functions  Issue 07/04 
  MICROMASTER 420    Operating Instructions 
58  6SE6400-5AA00-0BP0  
If the various prerequisites are fulfilled and the appropriate conditions present, then 
after the motor has been connected and the power connected, then the following is 
possible with the factory setting: 
 The motor can be started and stopped   (via DIN1 with external switch) 
 The direction of rotation can be reversed  (via DIN2 with external switch) 
 Faults reset          (via DIN3 with external switch) 
 A frequency setpoint can be entered   (via ADC with external    
      potentiometer, default setting of 
      the ADC: unipolar voltage input) 
 The frequency actual value can be output  (via DAC,  
      DAC output: current output) 
The potentiometer and the external switches can be connected through the drive 
inverter internal power supply, as shown in Fig. 3-13. 
Digital Inputs
I/O
Ack
< 4.7 k Ω
Analog input
 
Pre-assignment of the digital inputs DIN1 to DIN3, refer to Table 3-7.
 
Fig. 3-13  Recommended wiring for the factory setting 
If settings have to be made which go beyond the factory setting, then depending on 
the complexity of the application, when commissioning the drive system, the 
particular function description as well as the parameter list including function charts 
must be carefully taken into consideration.