Issue 07/04  3  Functions 
MICROMASTER 420    Operating Instructions   
6SE6400-5AA00-0BP0 
93 
NOTE 
When the filter time constant P0753 (ADC-PT1) is increased, this smoothes the 
ADC input signal therefore reducing the ripple. When this function is used within a 
control loop, this smoothing has a negative impact on the control behavior and 
immunity to noise (the dynamic performance deteriorates). 
Wire breakage monitoring 
The wire breakage monitoring (refer to Fig. 3-25) is set using parameters P0756 
and P0761. If the input signal of the analog input falls below the wire breakage 
threshold (0.5 
*
 P0761), then after the time in P0762 expires, fault F0080 is output 
and the status bit is set in parameter r0751. 
t0
Signal loss
t0
P0761
V
1
P0761  0,5 ⋅
10
P0762
r0751
t0
1
F0080
Fault acknowl.
Analog input
t0
Act. ADC after scaling
r0755
 
Fig. 3-26  Wire breakage monitoring 
The following secondary conditions/limitations apply to the wire breakage 
monitoring: 
 The monitoring function must be activated using parameter P0756  
 Width of the ADC dead zone P0761 > 0 
 Wire breakage monitoring if the ADC input quantity ≤ 0.5 
*
 P0761 
Note 
 The wire-breakage monitoring function is only possible for unipolar analog 
inputs. 
 Input range 0 to 0.5 
*
 P0761 of the analog input must be excluded when 
activating the wire breakage monitoring for normal operation.