5 MICROMASTER 420 specifications Issue 07/04
MICROMASTER 420 Operating Instructions
158 6SE6400-5AA00-0BP0
Table 5-1 MICROMASTER Performance Ratings
Feature Specification
Mains operating voltage
and
Power ranges
1 AC 200 V to 240 V
± 10 % 0,12 kW – 3,0 kW (0,16 hp – 4,0 hp)
3 AC 200 V to 240 V
± 10 % 0,12 kW – 5,5 kW (0,16 hp – 7,5 hp)
3 AC 380 V to 480 V
± 10 % 0,37 kW – 11,0 kW (0,50 hp – 15,0 hp)
Input frequency 47 Hz to 63 Hz
Output frequency 0 Hz to 650 Hz
Power factor
0,7
Inverter efficiency 96 % to 97 %
Overload capability 50 % overload capability for 60 s within 5 min period referred to the rated output
current
Inrush current Less than nominal input current
Control method Linear V/f Control; Linear V/f with Flux Current Control (FCC),
Quadratic V/f Control; Multi-point V/f control
Pulse frequency 2 kHz to 16 kHz (2 kHz steps)
Fixed frequencies 7, programmable
Skip frequencies 4, programmable
Setpoint resolution 0.01 Hz Digital, 0.01 Hz Serial, 10 bit Analogue
(motor potentiometer 0.1 Hz [0.1% (in PID mode)])
Digital inputs 3, programmable (isolated), switchable active high / active low (PNP/NPN)
Analogue input 1, (0 to 10 V) used for frequency setpoint or PI feedback signal, scalable or
usable as 4
th
digital input
Relay output 1, programmable 30 V DC / 5 A (resistive), 250 V AC / 2 A (inductive)
Analogue output 1, programmable (0 mA to 20 mA)
Serial interface RS-485, Option RS-232
Electromagnetic compatibility Optional EMC filters to EN55011 Class A or B,
also Internal Class A filters available
Braking DC braking, compound braking
Protection level IP20
Temperature range
-10
°C to +50 °C (14 °F to 122 °F)
Storage temperature
-40
°C to +70 °C (-40 °F to 158 °F)
Humidity < 95 % RH – non-condensing
Operational altitudes up to 1000 m above sea level without derating
Protection features Undervoltage , Overvoltage, Overload, Ground Faults, Short circuit, Stall
Prevention, Motor Blocking Protection, Motor Overtemperature, Inverter
Overtemperature, Parameter Interlock
Standards UL, cUL, CE, C-tick
CE Marked Conformity with EC Low Voltage Directive 73/23/EEC
and Electromagnetic Compatibility Directive 89/336/EEC