Table 3-19  BICO parameters for ramp-function generator 
Parameter Description 
P1140  BI: RFG enable  The ramp-function generator output is set to 0 if the 
binary signal = 0. 
P1141  BI: RFG start  The ramp-function generator output keeps its actual 
value if the binary signal = 0. 
P1142  BI: RFG enable setpoint  If the binary signal = 0, then the ramp-function 
generator input
 is set to 0 and the output is reduced 
to 0 via the ramp-function generator ramp. 
 
The ramp-function generator itself is enabled after the pulses have been enabled 
(inverter enable) and after the excitation time has expired (P0346). After limiting to 
the maximum speeds for the positive and negative directions of rotation (P1082, 
-P1082 or 0 Hz for the direction of rotation inhibit) the setpoint speed for the control 
is obtained (r1170). 
NOTE 
The maximum drive inverter frequency is defined in the setpoint channel using 
parameter P1080. The maximum possible frequency is 650 Hz.