3  Functions  Issue 07/04 
  MICROMASTER 420    Operating Instructions 
128  6SE6400-5AA00-0BP0  
The number of start attempts is specified using parameter P1211. The number is 
internally decremented after each unsuccessful attempt. After all attempts have 
been made (as specified in parameter P1211), automatic restart is cancelled with 
message F0035. After a successful start attempt, the counter is again reset to the 
initial value. 
NOTE 
 The "Flying restart" function (refer to Section 3.16) must be additionally 
activated if, for an automatic restart, the drive inverter is to be connected to a 
motor which may already be spinning. 
DANGER 
 For longer line supply failures (blackouts)and when the automatic restart 
function is activated, over a longer period of time it may be assumed that 
MICROMASTER is powered-down. However, when the line supply returns, 
motors can automatically start to run again without any operator intervention.  
 If the operating range of the motors is entered in this status, this can result in 
death, severe injury or material damage.