2  Installation  Issue 07/04 
  MICROMASTER 420    Operating Instructions 
32  6SE6400-5AA00-0BP0  
2.4.4 Avoiding Electro-Magnetic Interference (EMI) 
The inverters are designed to operate in an industrial environment where a high 
level of EMI can be expected. Usually, good installation practices will ensure safe 
and trouble-free operation. If you encounter problems, follow the guidelines stated 
below. 
Action to Take 
 Ensure that all equipment in the cubicle is well grounded using short, thick 
grounding cable connected to a common star point or busbar 
 Make sure that any control equipment (such as a PLC) connected to the 
inverter is connected to the same ground or star point as the inverter via a 
short thick link. 
 Connect the return ground from the motors controlled by the inverters directly 
to the ground connection (PE) on the associated inverter 
 Flat conductors are preferred as they have lower impedance at higher 
frequencies 
 Terminate the ends of the cable neatly, ensuring that unscreened wires are as 
short as possible 
 Separate the control cables from the power cables as much as possible, 
using separate trunking, if necessary at 90º to each other. 
 Whenever possible, use screened leads for the connections to the control 
circuitry 
 Ensure that the contactors in the cubicle are suppressed, either with R-C 
suppressors for AC contactors or 'flywheel' diodes for DC contactors fitted to 
the coils. Varistor suppressors are also effective. This is important when the 
contactors are controlled from the inverter relay 
 Use screened or armored cables for the motor connections and ground the 
screen at both ends using the cable clamps 
 
 
WARNING 
Safety regulations must not be compromised when installing inverters!