Accessing the connection compartment through the rear
144 NXAIR / 40 kA 110-0084.9 / 15
(4)
Rear wall with handle
(5)
Bolts to loosen
Fig. 211: All panel versions except for contactor panels with panel width 435 mm
and switch-disconnector panel: Removing the rear wall
Access to the connection compartment through the rear side of the panel is given.
Contactor panels with panel width 435 mm only:
Remove the connecting elements from one of the vertical ledges (1):
15 bolts M8x20 with contact washers
Remove the vertical ledge, and store it together with the associated connecting elements.
Proceed in the same way with the other vertical ledge.
(1)
Vertical ledges
Fig. 212: Contactor panels with panel width 435 mm only:
30 bolts in the ledges