Electrical connections
162 NXAIR / 40 kA 110-0084.9 / 15
(1)
Cable connection point
(2)
Cable lug
(3)
Cable sealing end
(4)
Shielding cover
(5)
Earth connections with
connection bolt
size M12x35
(6)
Cable clamp at the cable
bracket
(7)
Deep bottom pan
(8)
Heat-shrinkable splitting cap
Fig. 231: Side view of connection compartment with
three-core cables
Preconditions
The panel is placed on its assigned place of installation
Access to the connection compartment is established
Deep bottom pan available from the supplementary equipment for the switchgear
Procedure
Take the pre-assembled bottom pan from the supplementary equipment of the delivery.
For further installation, the pre-assembled bottom pan must be disassembled, so that the parts can be
installed individually in the base frame of the connection compartment. To do this, unscrew the
connecting elements (3), (4) and (5) completely, and store the individual components and the
connecting elements for later use.
If there is a substation earth in the panel, remove and dispose of the cover plate (6) for elongated
cutout. If there is no substation earth in the panel, keep the cover plate (6) for elongated cutout in the
deep bottom pan.
Fig. 232: Pre-assembled bottom pan
(1)
Front plates
(2)
Side plates
(3)
8 bolts M8x16
(4)
4 nuts M8 plus plain
washers size 8 acc. to
ISO 7093
(5)
16 bolts M8x20 plus
plain washers size 8 acc. to
ISO 7093
(6)
Cover plate for
elongated
cutout in deep bottom
7
1
3
2
4
5
6
8
3
5
2
1
4
6