Electrical connections
110-0084.9 / 15 NXAIR / ≤ 40 kA 163
Set 1 side plate each down onto 4 standing studs size M8, each on the left and right side in the
connection compartment.
Set 1 front plate each down onto 4 standing studs size M8, each at the front and rear side in
the connection compartment.
Take the bag unit with the connecting elements from the supplementary equipment of the
delivery.
Bolt the front and side plates to the studs of the connection compartment using the connecting
elements (1) and (2) from the bag unit.
Bolt the front and side plates together using the stored connecting elements (3).
If necessary, bolt the cover plate (4) to the studs of the connection compartment using the
connecting elements.
Fig. 233: Assembly of the front and side plates
Hexagon nut size M8, contact washer size 8
Hexagon nut size M8, contact washer size 8, plain washer size 8 acc. to ISO 7093
Hexagon head bolt size M8x16, contact washer size 8
Cover plate with fixing nut size M8
Cut an opening into the rubber sleeve that fits the diameter of the cable.
Lead the cable through the opening in the rubber sleeve.
Split the three-core cable into single cables, mount the heat-shrinkable splitting cap, and lead
the earthing connection out.