Electrical connections
110-0084.9 / 15 NXAIR / 40 kA 169
Cut an opening into the rubber sleeve that fits the diameter of the cable.
Lead the cable through the opening in the rubber sleeve.
Split the three-core cable into single cables, mount the heat-shrinkable splitting cap, and lead
the earthing connection out.
Connect one single cable each with a cable sealing end. Connect one cable sealing end each
with a cable lug.
Lay the components of the floor cover into the bottom pan. While doing so, insert the rubber
sleeve in the floor cover.
Bolt the components of the floor cover together using the connecting elements (1).
Fig. 240: Assembly of the floor cover
(1)
4 bolts M8x20
(2)
2 floor covers
(3)
Rubber sleeve
Insert the cable bracket (1), and put it in position.
Fasten the cable bracket using the connecting elements (2).
Fig. 241: Assembly of the cable brackets
(1)
Cable bracket
(2)
4 nuts M8 plus 4 plain washers
size 8 acc. to ISO 7093