Loading...
Closing the connection compartment / connection duct
110-0084.9 / 15 NXAIR / 40 kA 187
Lid of metal cover and associated connecting elements available:
2 bolts M8x20 with contact washers
Wiring duct cover and associated connecting elements available:
2 bolts M8x20 with contact washers
Labyrinth and associated connecting elements available:
11 bolts M8x16 with contact washers
2 nuts M8 with contact washers
Procedure
Install the bushing plate.
Fix the bushing plate by screwing the bolts hand-tight:
8 bolts M8x20 with contact washers and plain washers size 8
acc. to ISO 7093 (1)
3 bolts M8x20 with contact washers (2)
Tighten the bolts with a tightening torque of 25 Nm.
Fig. 272: 11 bolted joints on bushing plate
Connect the 3 connecting cables (4) for the removable voltage transformers with the cable
connections / bar connections.
Fix the connecting leads (4). To do this, mount the connecting elements (3) and tighten hand-
tight:
3 nuts M8 with contact washers and plain washers
Tighten the nuts with a tightening torque of 25 Nm.