Assembling the panels
70 NXAIR / ≤ 40 kA 110-0084.9 / 15
Fig. 79: Side view of 3150 A / 4000 A busbar assembly,
feeder 400 A
Arrowhead indicates the
inserting direction of the
bolt
Busbar version for busbar current metering panel for U
r
≤ 12 kV
In the busbar current metering panel, the busbars of phases L1 and L3 are directly bolted onto the current
transformers. The busbar of phase L2 has to be connected with a feeder bar. Thereby, observe the inserting
direction as shown below.
Bolt, conical spring washer
Nut, conical spring washer
Fig. 80: Busbar current metering panel
:
Busbar assembly phase L2
(for example,
2500 A busbar)
Fig. 81: Details; the arrowhead indicates the
inserting direction of the bolt