Assembling the panels
82 NXAIR / 40 kA 110-0084.9 / 15
Mounting the transverse partition
Mounting the transverse partition, all panel versions except for contactor panels with panel width
435 mm and switch-disconnector panel
Slide the transverse partition plate (2) onto the busbars.
Screw the transverse partition plate together with the busbar compartment at the
upper and lower edges using connecting elements (1), (3).
(1)
2 hexagon head
bolts M8x20 and
plain washers size
8.4 mm
(2)
Transverse
partition plate
(3)
2 bolts M8x20 with
contact washers
Fig. 96: Mounting the transverse partition plate from the right, panel depth
1500/1540/1650 mm
Mounting the transverse partition on contactor panel with panel width 435 mm
On contactor panels with panel width 435 mm, the transverse partition plate is not fastened before the adjacent
panel has been approached. The 3 bolted joints of the transverse partition plate are fitted through the busbar
compartment of the adjacent panel.
INFORMATION
Mounting the transverse partition plate on contactor panels with panel width
435 mm:
Approach the adjacent panel first, then fasten the transverse partition plate.
Slide the transverse partition plate (2) onto the busbars.
Approach the adjacent panel and fasten the transverse partition plate between the
two busbar compartments at the upper edge using 2 hexagon head bolts size M8x20
and plain washers size 8.4 mm (1) and at the lower edge using hexagon socket head
bolt size 6 (3).
1
2
3