EasyManua.ls Logo

Siemens NXAIR - Page 83

Siemens NXAIR
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Assembling the panels
110-0084.9 / 15 NXAIR / 40 kA 83
Fig. 97: Contactor panels with panel width 435 mm:
Mounting the transverse partition plate from the right
Mounting the transverse partition on switch-disconnector panel
On switch-disconnector panels, the transverse partition plate is fastened on both right and left sides even if
there is no transverse partition plate for the rest of the panels. In the case of the switch-disconnector panel is
end panel, transverse partition plate is fastened on the one side.
Slide the transverse partition plate (2) onto the busbars on the right and left sides.
Screw the transverse partition plate together with the busbar compartment at the upper and the lower
edges using connecting elements:
2 hexagon head bolts M8x20 and plain washers size 8.4 mm (1)
2 bolts M8x20 with contact washers (3)
Fig. 98: Mounting the transverse partition plate
from the left on the switch-disconnector
panel
Fig. 99: Mounting the transverse partition plate
from the right on the switch-
disconnector panel
1
2
2
2
3
2
2
3
1