Assembling the panels
88 NXAIR / ≤ 40 kA 110-0084.9 / 15
Insert the panel connection links (3) between two switching-device compartments in the front area.
Fig. 106: Panel connection link
Wiring duct cover in switching-device compartment
Sharp-edged sheets
The metal parts of the wiring duct covers may have sharp edges. Sharp-edged
sheets inside the switchgear can cause injuries by getting cut and damage cables.
Put on personal protective equipment (e.g. cut-resistant gloves and arm
sleeves).
When working inside the switchgear, it must be observed that cables do not
touch any sharp-edged sheets. Cover sharp-edged spots, if required.
Foreign objects
Possible malfunctioning and switchgear damage caused by foreign objects.
Remove all foreign objects from the switching-device compartment, e.g.:
• Tools
• Unused installation material
• Packing material
• Cleaning material