Assembling the panels
110-0084.9 / 15 NXAIR / 40 kA 89
Remove 2 hexagon head bolts M8x20 each from the upper and the lower wiring duct cover on
the left inner side of the panel in the switching-device compartment.
Remove the upper and the lower wiring duct cover from the switching-device compartment.
Fig. 107: Removing the wiring duct cover
INFORMATION
The necessary bolting elements are delivered in a bag unit together with each panel.
The bag units are attached to the sheet-steel enclosure of the busbar compartment.
For bolting the panels together, use bag unit with order number
110-0788.3.
After removing the connecting elements, the packing materials of the bag
unit must be disposed of in an environmentally compatible way.
The bag units can be re-ordered individually.
Take 7 bolts M8x25 (hexagon head bolt with contact washer) and 7 plain washers size 8
according to ISO 7093 from the bag unit supplied, and screw them from the left inner side of
the switching-device compartment into the adjacent switching-device compartment.
(1)
Hexagon head bolt M8x20
(2)
Upper wiring duct cover
(3)
Lower wiring duct cover