EasyManua.ls Logo

Siemens PCS 7 - Basic Procedure

Siemens PCS 7
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Basic procedure
Note
If the encrypted communication is enabled on a PC station, this PC station can only establish
communication connections to PC stations on which the same PSK is configured.
Note the following example: Communication with inconsistent settings for encrypted
communication in a plant
1. Switch on migration mode for all PC stations:
Leave the PSK unchanged and select the "Migration mode" check box.
2. Disable encrypted communication for all PC stations:
Clear the "Encrypted communication" check box.
3. Enable new PSK for all PC stations:
Select the "Encrypted communication" check box, enter the new PSK and select the
"Migration mode" check box.
4. Switch off migration mode for all PC stations:
Leave the PSK unchanged and clear the "Migration mode" check box.
Example: Communication with inconsistent settings for encrypted communication in a plant
Example of an initial situation
System Communication PSK
Server_A Encrypted, migration mode enabled AAA
Client_1 Encrypted, migration mode enabled AAA
Server_B Encrypted, migration mode enabled 111
Client_2 Unencrypted -
Reaction
Type of communica‐
tion between the PC
stations
Server_A Client_1 Server_B Client_2
Server_A - Encrypted No connection Unencrypted
Client_1 Encrypted - No connection Unencrypted
Server_B No connection No connection - Unencrypted
Client_2 Unencrypted Unencrypted Unencrypted -
Additional information
Section "How to access PC stations outside a subnet (Page 112)"
Installing PC stations
5.7 Preparing PC stations
PCS 7 - PC Configuration (V8.2)
118 Installation Manual, 03/2016, A5E36200050-AB