Technical data
7.4 Technical data, 400 V inverters
Power Module PM240-2
78 Hardware Installation Manual, 12/2015, A5E33294624B AD
Degree of protection ac-
cording to EN 60529
Chassis de-
vices
IP20
IP20,
Must be installed in a control cabinet
Must be installed in a control cabinet
at the control cabinet panel
Ambient temperature FSA … FSC:
LO base load power without derating:
HO base load power without derating:
LO/HO base load power with derating:
-10 °C … +40 °C
-10 °C … +50 °C
FSD … FSF:
LO base load power without derating:
HO base load power without derating:
LO/HO base load power with derating:
-20 °C … +40 °C
-20 °C … +50 °C
Restrictions for special ambient conditions (Page 92)
For the maximum permissible ambient temperature, also observe the permissible ambient
temperatures for the Control Unit and possibly operator panel (IOP or BOP-2) .
Ambient conditions accord-
ing to EN 60721-3-3
FSA … FSC: Protected against damaging chemical substance, according to environmental
FSD … FSF Protected against damaging chemical substance, according to environmental
Class 3C3
Temperature during stor-
age according to EN
60721-3-3
-40 °C … +70 °C
Pollution according to EN
suitable for environments with degree of pollution 2, condensation not permissible
Shocks and vibration ac-
cording to EN 60721-3-1
• Long-term storage in the transport packaging according to Class 1M2
• Transport in the transport packaging according to Class 2M3
• Vibration in operation according to Class 3M2
Installation altitude without derating:
up to 1000 m above sea level
up to 4000 m above sea level
Restrictions for special ambient conditions (Page 92)
Approvals FSA … FSC
cULus, CE, C-tick, KCC
cULus, CE, C-tick, SEMI F47, KCC, WEEE, RoHS, EAC