Technical data
7.5 Technical data, 690 V inverters
Power Module PM240-2
Hardware Installation Manual, 12/2015, A5E33294624B AD
91
Table 7- 28 PM240-2, IP20, FSF, 3 AC 500 V … 690 V
Article No. - without filter
Article No. - with filter
6SL3210-…
6SL3210-…
…1PH31-4UL0
…1PH31 4AL0
LO base load power
LO base load input current
LO base load output current
132 kW
137 A
142 A
HO base load power
HO base load input current
HO base load output current
110 kW
122 A
115 A
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NE1 225-0 / 200 A
200 A
Power loss without filter
Power loss with filter
2.56 kW
2.59 kW
Required cooling air flow
153 l/s
Weight without filter
Weight with filter
60 kg
64 kg
7.5.3
Current derating depending on the pulse frequency, 690 V inverters
Article number
LO base load output current for a pulse frequency of …
[A]
2 kHz
4 kHz
6SL3210-1PH21-4L0
14
8.4
6SL3210-1PH22-0❒L0
19
11.4
6SL3210-1PH22-3❒L0
23
13.8
6SL3210-1PH22-7❒L0
27
16.2
6SL3210-1PH23-5❒L0
35
21
6SL3210-1PH24-2❒L0
42
25.2
6SL3210-1PH25-2❒L0
52
31.2
6SL3210-1PH26-2❒L0
62
37.2
6SL3210-1PH28-0UL0
80
48
6SL3210-1PH31-0❒L0
100
60
6SL3210-1PH31-2❒L0
115
69
6SL3210-1PH31-4❒L0
142
85.2
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens PM240-2 and is the answer not in the manual?

Siemens PM240-2 Specifications

General IconGeneral
Input Voltage380 ... 480 V 3 AC
EfficiencyUp to 98%
Protection ClassIP20
Communication InterfacesPROFIBUS, PROFINET, USS, Modbus RTU
Storage Temperature Range-25 ... 70 °C
Relative Humidity5 ... 95 % (no condensation)
Shock Resistance15 m/s² (1.5 g) for 11ms
Frame SizeFS A to FS F
Operating Temperature Range-10 ... 50 °C (without derating), -10 ... 60 °C (with derating)