Description
2.5 Electronic trip unit ETU600
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
117
ETU600 LSIG Hi-Z with LSIG GFx (GF extended) option plug
G: Ground-fault protection GF
Ground-fault protection GF Hi-Z
Method of ground-fault detection
Detection of the ground-fault current
through calculation of the summation
current in all phases of the N-
conductor (UREF protection zone
for high-impedance connection of the
external current transformers
UREF protection zone: Detection of
the ground-fault current through
calculation of the summation current
REF protection zone: Measurement of
the ground-fault current using an
external current transformer
If ground-fault protection GF Hi-Z is
activated
g
• Size 1 / 2: 100 … 2000 A
• Size 3: 400 … 2000 A
g
• For I
x
t = OFF: 0 … 5 s
• For I
x
t = ON at 3 x I
g
: 0 … 30 s
g def
For I
x
t = OFF: 0.05 … 0.5 s
If ground-fault protection GF Hi-Z is
activated
g
• Transformation ratio of the
current transformer (1 … 7000)
• Shunt (10 ... 1000 Ω)
• Secondary current via shunt
(11 ... 5000 mA)
g alarm
• Size 1 / 2: 100 … 5000 A
• Size 3: 400 … 5000 A