Description
2.5 Electronic trip unit ETU600
3WA1 air circuit breaker
116 Equipment Manual, 02/2023, 92310000002-06
ETU600 LSI, ETU600 LSIG, ETU600 LSIG Hi-Z
Protective function Setting range for parameter sets A
Settings with rotary coding switch
only possible in parameter set A
Reverse power protection RP (optional)
1)
The setting is limited depending on the breaking capacity of the set rated voltage.
ETU600 LSIG with LSIG GFx (GF extended) option plug
G: Ground-fault protection GF
Method of ground-fault detection
Detection of the ground-fault current
through calculation of the summation
current in all phases of the N-
conductor
Direct measurement of the ground-
fault current using a current
transformer
UREF protection zone: Detection of
the ground-fault current through
calculation of the summation current
REF protection zone:
Measurement of the ground-fault
current using an external current
g
Residual acquisition method
• Size 1 / 2: 100 … 2000 A
• Size 3: 400 … 2000 A
Direct acquisition method
g
g def
g alarm
Residual acquisition method
• Size 1 / 2: 100 … 5000 A
• Size 3: 400 … 5000 A
Direct acquisition method
g alarm