Description   
2.10 Zone-selective interlocking ZSI 
  3WA1 air circuit breaker 
196  Equipment Manual, 02/2023, 92310000002-06 
The following figure shows a ZSI system with one fuse and four circuit breakers. Due to 
the adjustable delay t
ZSI
, the break time can be reduced by a ZSI system even when 
fuses and circuit breakers are used simultaneously. 
The delay t
ZSI
 of the short-time-delayed short-circuit protection is matched to the fuse -
F1 with 0.2 s in the following example. The grading times t
sd
 of the short-time-delayed 
short-circuit protection ST of the upstream circuit breakers are unchanged. 
For the power distribution system with three grading levels, faults A, B and C are 
considered in more detail.  
The left side of the figure shows the settings of the ZSI function and the delays for the 
short-time-delayed short-circuit protection ST. 
 
Fault scenario A 
•  The -F1 fuse switches off the short-circuit according to its characteristic curve. 
•  Depending on the level of the short-circuit current, the two -Q3 and -Q1 circuit 
breakers can also be excited by the short-circuit current. 
In this case, the -Q3 circuit breaker does not receive a control signal at the ZSI 
interface port A from a downstream grading level and would trip after the delay t
ZSI
 
0.2 s if a pick-up is pending. 
In the event of an excitation, it would send this excitation as a control signal via the 
ZSI interface port B to the -Q1 circuit breaker.