EasyManua.ls Logo

Siemens SENTRON 3WA1 - Page 199

Siemens SENTRON 3WA1
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
2.10 Zone-selective interlocking ZSI
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
197
Fault scenario B
The -Q3 and -Q1 circuit breakers detect the short-circuit. Via the ZSI system, the -Q1
circuit breaker is informed of the pick-up of -Q3. This prevents tripping of -Q1 after
the delay t
ZSI
.
The -Q3 circuit breaker does not receive any pick-up information from a downstream
circuit breaker at the ZSI interface port A. Therefore, the -Q3 circuit breaker trips
after the set delay t
ZSI
0.2 s for the short-time-delayed short-circuit protection ST.
If the fault current cannot be switched off by the -Q3 circuit breaker, tripping of -Q1
as back-up protection takes place after the delay time t
sd
.
Fault scenario C
The -Q1 circuit breaker detects the short-circuit and does not receive any information
about the pick-up of a downstream circuit breaker.
Therefore -Q1 trips after the delay t
ZSI
0.2 s.
It can also be seen in this example that when fuses and circuit breakers are used, the
load on the power distribution system in the event of a short-circuit is significantly
reduced by the ZSI system.
This reduction in load can also be seen in the two grading diagrams. On the left, the
grading times for a fault in B and on the right for a fault in C are shown.
For both faults, tripping takes place after the delay t
ZSI
.

Table of Contents

Related product manuals