Prepare Engineering
SICAM RTUs, SICAM AK 3 User Manual 177
DC2-028-2.03, Edition 07.2016
3.5 Loadable Firmwares
The modular system SICAM AK 3 consists of system elements, that are designed for specific
functions:
Master control element
Central processing and coordination
Processing and communication element(s)
Expansion of peripheral elements and protocol elements
Peripheral element(s)
Acquisition and output of process signals
Protocol element(s)
Communication with control center and further automation units
For the implementation of the respective functions, special firmwares are provided. The func-
tionality of each system element is adjustable by means of parameters.
As a partner of Siemens you are able to download all the current firmware revisions for your
system via the internet under www.siemens.com/sicam.
Examples:
System Element Item Number Designation
CPCX26 Central pro-
cessing/communication
SC2-016-1 CPCX26 Revision history
SC2-016-1.XX/53 CPCX26 TB II update
PCCX26 Periphery interfac-
ing, control, communication
SC2-019-1 PCCX26 Revision history
SC2-019-1.XX/53 PCCX26 TB II update
ETA4 Ethernet interface
IEC 60870-5-104
SC0-581-1 ETA4 Revision history
SC0-581-1.XX/53 ETA4 TB II update
BISX26 Binary signal input
8x8 IEC
SC2-112-1 BISX26 Revision history
SC2-112-1.XX/53 BISX26 TB II update
In order that the corresponding system elements work and can be parameterized, the respec-
tive
Firmware codes must exist in the target system
Toolbox update must be stored in the SICAM TOOLBOX II
The respective TB II update contains the firmware code for the relevant system element, as
well as the master data for the SICAM TOOLBOX II.
How to load firmwares into a target system, you find in section 5.5.1, Procedure.