Service
SICAM RTUs, SICAM AK 3 User Manual 231
DC2-028-2.03, Edition 07.2016
5.5.1.1 Interrogation of Firmware Revision
The firmware revisions of all configured system elements (basic system element, peripheral
element, protocol elements) can be displayed and printed with the tool "Revision Interrogation
and Display" for a selected automation unit.
You find further details on the tool in the SICAM TOOLBOX II Online Help, chapter "Service
Programs", section "Revision Interrogation and Display".
5.5.1.2 Import of Firmware into the SICAM TOOLBOX II
New firmware codes can be loaded into the SICAM TOOLBOX II with the tool "Master Data
Update". Thereto belong
Libraries for the tool OPM II
Firmwares of SICAM RTUs system elements
You find the details thereto in the SICAM TOOLBOX II Online Help, chapter "OPM II", section
"Master Data Update".
An additional option provides the tool "Live Update". You find the information thereto in the
SICAM TOOLBOX II Online Help, chapter "Service Programs", section "Live Update".
5.5.1.3 Loading of Firmware into the Target System
Firmware codes that are existing in the SICAM TOOLBOX II can be loaded with the tool "Load
Firmware" into the connected target systems.
The loading of the firmware is related to all loadable system elements of the automation unit:
Master control element
Processing and communication element
Peripheral elements
Protocol element
For the loading of firmware the corresponding modules must be installed and configured. After
the loading procedure the target system performs a startup. Depending on the size and num-
ber of loaded files a startup can take up to 10 minutes.
With loading of firmwares the target system checks, whether the corresponding system ele-
ments are already configured. If this is the case, the firmware is updated for all configured sys-
tem elements.