Service
214 SICAM RTUs, SICAM AK 3 User Manual
Edition 07.2016, DC2-028-2.03
Startup (step) RY ER W BBD INT ACT EXT CPY HLT Error
Check, whether firmware code of
the lower-level system elements
(processing and communication
elements
1)
, protocol elements,
peripheral elements) is current
˜
If not, the load firmware is loaded at a later time
Revision check of the parameters
in the parameter memory of the M-
CPU
˜
˜
1)
If the parameters are not current, they are loaded
from the flash card
Check parameter memory (flash
PROM)
˜ V
Checksum error of the parameters
Firmware is shutdown
Startup is aborted
Check whether the parameterized
configuration corresponds with the
physical configuration (processing
and communication elements
1)
,
protocol elements, peripheral
elements)
˜
Configuration error
The incorrectly configured or defective sys-
tem element is not operational
Loading of the parameters to the
lower-level protocol- and peripher-
al elements
˜
Too little memory on the protocol element or
peripheral element
Firmware on the protocol element or periph-
eral element is shutdown
Check of the parameter contents
˜
Parameter error
Diagnosis information is set
Startup concluded without error
˜
x
2)
Startup concluded with error
˜ ˜
x
1)
applies for the main processor (M-CPU) on the master control element
2)
flashes for approx. 20s after replacement of the master control element resp. of a processing and communication element

Table of Contents