9 Operation at Use of the Display
9.4 Parameterization
293SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
1) After the communication parameters have been changed, the device restarts. For this purpose, a prompt
is displayed which you must acknowledge with Ok.
Table 9-6 IP Address Settings
Parameter Default Setting Setting Range
MAC address fixed
IP address
1)
192.168.0.55 Any
0.0.0.0 = DHCP
Subnet
1)
255.255.255.0 Any
Gateway
1)
192.168.0.1 Any
Table 9-7 Ethernet Communication Settings
Parameter Default Setting Setting Range
Bus protocol Modbus TCP none
Modbus TCP
IEC 61850
Both
Ethernet Communication - Modbus TCP Bus Protocol
Access rights for port 502 full full
read only
Keepalive time 10 s 0 s = switched off
1 s to 65,535 s
Communication monitoring time 600 * 100 ms 0 s = none
100 ms to 6 553 400 ms
Set user port number
1)
No No
Yes
User port number
1)
(only settable if Set user port number
is parameterized with yes)
10 000 10 000 to 65 535
Access right for user port
(only settable if Set user port number
is parameterized with yes)
full full
read only
Ethernet Communication - IEC 61850 Bus Protocol
IED Name SICAM_Q100_01 read only
Voltage - Deadband 5 % 1 % to 5 % in increments of 1 %