9 Operation at Use of the Display
9.4 Parameterization
294 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
1) After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later re-open these connections.
Current - Deadband 5 % 1 % to 5 % in increments of 1 %
Power - Deadband 5 % 1 % to 5 % in increments of 1 %
Power factor - Deadband 5 % 2% to 5 % in increments of 1 %
Frequency - Deadband 0,05 0.02 %
0.05 %
Table 9-8 Serial Communication Settings – Modbus RTU and Modbus RTU Master Bus Protocols
Parameter Default Setting Setting Range
Bus protocol Modbus RTU None
Modbus RTU
Modbus Master
Bus Protocol Modbus RTU (Slave)
Device address 1 1 to 247
Baud rate 19 200 bit/s For the selection, see Chapter 15
Parity Even For the selection, see Chapter 15
Access rights Full Full
Read only
Communication supervision time 600 * 100 ms 0 s = none
100 ms to 6 553 400 ms
Bus Protocol Modbus RTU Master
Baud rate 19 200 bit/s For the selection, see Chapter 15
Parity even For the selection, see Chapter 15
Additional inter-character timeout 1 ms 0 ms to 100 ms
Maximum 0x/1x register gap 40 0 to 200
Maximum 3x/4x register gap 10
Table 9-7 Ethernet Communication Settings (cont.)