EasyManua.ls Logo

Siemens SIMATIC LOGO! CMR2020 - SMS Error Messages

Siemens SIMATIC LOGO! CMR2020
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
7.3 SMS message structures and examples
LOGO! CMR2020 / LOGO! CMR2040
Operating Instructions, 09/2014, C79000-G8976-C356-01
121
The number of SMS jobs/time is limited
The CMR stores a limited number of SMS send jobs in a job queue.
Sending an SMS message may take several seconds due to the delayed transfer in the
mobile wireless network.
To make sure that all SMS messages are sent within the required time:
Adapt the length of the interval for large amounts of data to be sent cyclically, e.g. PI-
SMS messages (monitor SMS) accordingly.
Make sure that there is enough time between different actions sending PI-SMS
messages.
If, for example, a PI-SMS message requested using SMS was sent incompletely, repeat your
request SMS message.
SMS error messages
You will find a list of all possible error messages in SMS error messages (Page 121).
7.3.2
SMS error messages
Message
Possible causes
OK
The SMS command was executed successfully.
Invalid Command
SMS keyword could not be recognized.
Check the uppercase/lower case characters and syntax.
Invalid Parameter
Transfer parameter not correct; password not correct.
Not successful
Values could not be set or read.
Try again
The CMR is currently being reconfigured. The request
cannot be processed.
No connection to LOGO! BM
LOGO! BM not activated or wrong IP address set.
Cable between LOGO! BM and LOGO! CMR discon-
nected.
No GPS signal
GPS not configured.
GPS signal cannot be received because there is no line
of sight to the GPS satellite.