Application examples
5.4 Time-of-day synchronization
LOGO! CMR2020 / LOGO! CMR2040
Operating Instructions, 09/2014, C79000-G8976-C356-01
43
5.4
Time-of-day synchronization
Time-of-day synchronization for the CMR can be configured using three time-of-day
synchronization methods.
The time-of-day synchronization method is set in the configuration on the "System" page in
the "System time" (Page 58) tab:
Synchronization with an external NTP server accessible via the mobile wireless network.
Time of day from the GPS signal: The GPS antenna must be connected.
Time of day from the mobile wireless network
The availability of the time of day depends on the mobile wireless provider.
Note
The CMR does not set itself automatically
to a time of day synchronization method. You
n
eed to select a time of day synchronization method in the configuration.
Note
If you use time
-of-day synchronization of the BM via the CMR, disable the standard/daylight
saving setting on the BM to ensure a consistent time.
If you enable the time of day in the WBM, you can also make a setting in the WBM so that
the CMR also synchronizes the BM with the time of day (time-of-day forwarding).
"Forward time of day to LOGO! BM " is enabled:
Even if time-of-day synchronization is disabled, the time of day is forwarded to the LOGO!
BM . In this case, only the manual settings are transferred to the LOGO! BM .
The following figure provides an overview: