EasyManua.ls Logo

Siemens SIMATIC LOGO! CMR2020 - Disruptions and Their Possible Causes

Siemens SIMATIC LOGO! CMR2020
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
7.4 Disruptions and their possible causes
LOGO! CMR2020 / LOGO! CMR2040
132 Operating Instructions, 09/2014, C79000-G8976-C356-01
SMS command "DIAG? Response"
If the information cannot be sent with an SMS message, there is a 2nd SMS that starts with
"DIAG? Response".
Such a reply SMS message can appear as follows:
Example - the reply includes 2 SMS messages:
1. SMS
From: DEVICE-Name
LOGO! CMR2020 V1.0
GSM: registered
Attached for (ddd:hh:mm:ss): 000:00:03:36
2. SMS
DIAG? Response
GPRS: registered
Attached for (ddd:hh:mm:ss): 000:00:03:36
Network: Vodafone.de
IP: 77.25.26.11
Signal Quality: good (CSQ:29/-55dBm)
7.4
Disruptions and their possible causes
Disruption
Meaning
Solution
Error LED lit red
No connection to the BM
Wrong PIN
No SIM card but the mobile wireless
interface is activated
To obtain information on other possible
causes of error, it is best to check the
log events in the diagnostics buffer.
Check the connections/run the
PING test
Unlocking the SIM card
Inserting the SIM card
Error LED flashes red
Duplicate IP address Correct the IP address
No LED display
Power supply too weak
The CMR is in the shut down status
Correct the power supply according
to the Technical specifications
(Page 143)
No positioning possible
Bad GPS reception
Antenna not or not correctly
plugged in
GPS reception is normally only
possible outdoors: GPS reception is
not possible in enclosed spaces.
Check the connector

Table of Contents