EasyManua.ls Logo

Siemens SIMATIC LOGO! CMR2020 - Page 133

Siemens SIMATIC LOGO! CMR2020
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
7.4 Disruptions and their possible causes
LOGO! CMR2020 / LOGO! CMR2040
Operating Instructions, 09/2014, C79000-G8976-C356-01
133
Disruption
Meaning
Solution
Bad or no time-of-day synchronization
using NTP
Bad mobile wireless reception
Wrong configuration in the WBM
Mobile wireless interface deactivat-
ed
Incorrect NTP server name or incor-
rect IP address
Correct the alignment of the anten-
na
Activate the mobile wireless inter-
face in the WBM
Check the configuration of the mo-
bile data connection in the WBM
No SMS reception
SMS reception deactivated
Bad mobile wireless reception
User not registered or authorized
Activate SMS reception in the WBM
Check user rights in the WBM and if
necessary correct
Check the antenna position of the
mobile wireless antenna
No dial-in to the mobile wireless net-
work
PIN entered incorrectly three times
Mobile wireless interface deactivat-
ed in the WBM
See section Insert the SIM card and
enter the PIN (Page 33), unlocking
the SIM card
Activate the mobile wireless inter-
face in the WBM
Monitoring not working
Expected SMS messages config-
ured in the WBM are not received
Check in the WBM:
Are the assignments active?
Are the inputs/outputs connected
correctly?
Only if objects of the BM are moni-
tored:
Is the BM connected?
SMS message received in which there
are placeholders between 2 exclama-
tion points
A signal name specified in the WBM
does not exist or has been written
incorrectly. The incorrect or non-
existent signal name is then shown
in the message texts as follows:
[CMR_I1] becomes !CMR_I1!
Correct placeholders in the WBM

Table of Contents

Related product manuals