LOGO! CMR2020 / LOGO! CMR2040
Operating Instructions, 09/2014, C79000-G8976-C356-01
25
Installation, connecting up, commissioning
Safety notices on the use of the device
The following safety notices must be adhered to when setting up and operating the device
and during all associated work such as installation, connecting up or replacing devices.
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a
Limited Power Source (LPS). (This does not apply to 100 V...240 V devices.)
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1
must be connected to the power supply terminals. The power supply unit for the equipment
power supply must comply with NEC Class 2, as described by the National Electrical Code
(r) (ANSI / NFPA 70).
There is an additional requirement if devices are operated with a redundant power supply:
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
● Use only an external power supply that complies with EN 60950.
● The output voltage of the external power supply must not exceed 30 VDC.
● The output of the external power supply must be short-circuit proof.
The power supply unit to supply the CMR must comply with the requirements for a limited
power source according to IEC/EN 60950-1, section 2.5.
The external power supply for the CMR must meet the requirements for NEC class 2
circuits as specified in the National Electrical Code ® (ANSI/NFPA 70).
Note the information in this section and in the installation and operating instructions from the
manufacturer of the power supply.