Exchange of configuration data with STEP7 
  6.2 Message: SINEMA configuration not yet accepted 
SCALANCE SC-600 Web Based Management (WBM) 
Configuration Manual, 10/2021, C79000-G8976-C475-03 
355 
Solution 
1.  Open the relevant STEP 7 project in STEP 7 Basic / Professional 
2.  Open the project view. 
3.  Select the device in the project tree. 
4.  Select the "Go to network view" command in the shortcut menu. 
5.  Select the device in the network view. 
6.  In the shortcut menu of the selected device select the command "SCALANCE 
configuration > Save as start configuration". 
Result 
The configuration is saved on the device. The message is no longer visible in the display 
area. A configuration change directly on the device is no longer lost due to a restart of 
the device.