Structure of SIMATIC PCS 7 BOX
Process Control System PCS 7 - PCS 7 BOX
A5E00272813-01
3-7
3.4.2 SIMATIC PCS 7 BOX as Single Station System
The Box PC 620 serves as a combination PCS 7 engineering station and runtime
operator station. The automation function operates on the CPU 416-2 PCI
integrated in the Box PC 620 as a PCI card. The process I/Os are connected via
the integrated PROFIBUS DP interface of the CPU 416-2 PCI. Intelligent field
devices are configured via the on-board CP 5611 standard interface of the
Box PC 620.
1
2
3
4
5
6
7
8
9
0
.
+/-
Clear
Enter
ESC
Info
MEAS
ULTRAMAT 6
S
63,29
36,72
o CAL oLIM oAR o CODE
24V DC
DP/PA-Link
PROFIBUS PA
PROFIBUS DPPROFIBUS DP
PDM OS
Simatic Net
CP 5611
on board
CPU 416-2
PCI + PS
PCMCIA
card
Ethernet
on board
ES
PROFIBUS MPI/DPPROFIBUS MPI/DP
SIMATIC PCS 7 BOX
MPI/
DP DP
You can activate the complete preinstalled PCS 7 software (Engineering and
Runtime) and the PDM (Process Device Manager) with the corresponding
authorization for this configuration.
Note
The authorization for the PDM must be ordered separately.