Commissioning and Configuration
Process Control System PCS 7 - PCS 7 BOX
A5E00272813-01
4-11
4.2.7 Step 7: Setting Time Synchronization
WinCC and the CPU 416-2 PCI are synchronized with the local PC clock.
Requirement
In HW Config, the synchronization mode "As Slave" is set for the time
synchronization in the AS.
Follow These Steps:
1. Open the "TimeSyncCfg" dialog with the command Start > Simatic > PC Based
Control > WinAC Time Synchronization.
2. Activate the option "PC clock" under "Source" in the "Configuration" section of
the dialog.
3. Once you have made these settings, click the "Start" button to begin time
synchronization and then click "Close" to exit the dialog.
Additional Information
Manual Windows Automation Center WinAC Slot V3.4

Table of Contents