Programming via XML interface
10.3 XML commands
SIMATIC RF600
150 Configuration Manual, 11/2018, C79000-G8976-C386-07
Parameter
Parameter
Type
Values
Description
value_id Decimal value
0...9
0...4294967295 Unique command identifier
value_iPAddress IP address 1.0.0.1…
255.255.255.254
IP address of the reader
Parameter is ignored, if DHCP is acti-
vated:
value_dHCPEnable = True
value_
subNetMask
IP address 1.0.0.1…
255.255.255.254
Subnet mask of the reader
Parameter is ignored, if DHCP is acti-
vated:
value_dHCPEnable = True
value_gateway IP address 1.0.0.1…
255.255.255.254
Gateway of the reader
Parameter is ignored, if DHCP is acti-
vated:
value_dHCPEnable = True
value_
dHCPEnable
Fixed values True
False
Use of DHCP to assign the IP address.
10.3.2
Reader settings
This section describes all the commands with which you can control the configuration of the
reader.
10.3.2.1
setConfiguration
This command transfers a configuration to the reader. After confirming the configuration, this
is activated and stored permanently in the flash memory of the reader. To be able to work
with the newly created configuration, you need to restart the reader.
As an alternative, you can also load a configuration that was created using the WBM.
Note that the reply frame of the reader can take up to 20 seconds.
Command
<frame>
<cmd>
<id> value_id </id>
<setConfiguration>
<configData>
<![CDATA[value_configData]]>
</configData>
</setConfiguration>
</cmd>
</frame>