Installation
6.2 Installing the mounting rail
Automation system
System Manual, 01/2023, A5E03461182-AK
129
Dimensions for the drill holes
Table 6- 2 Dimensions for the drill holes
"Standard" mounting rails
"Longer" mounting rails
Length of the mounting
rail
Distance a
Distance b
160 mm
10 mm
140 mm
245 mm
10 mm
225 mm
482.6 mm
8.3 mm
466 mm
530 mm
15 mm
500 mm
830 mm
15 mm
800 mm
Additional fixing screws (for mounting rails > 530 mm)
For mounting rails longer than 530 mm, we recommend using additional fixing screws at
intervals of >482 mm on the identification groove.
Preparing the 2000 mm mounting rail for installation
To prepare the 2000 mm mounting rail for installation, proceed as follows:
1. Cut the 2000 mm mounting rail to the required length.
2. Mark the holes. The necessary dimensions can be found in the table "Dimensions for the drill
holes":
Two drill holes at the beginning and end of the mounting rail
Additional drill holes at equal intervals of 500 mm maximum, along the identification
groove
3. Drill the marked holes according to the selected type of fastening.
4. Ensure that there are no burrs or shavings on the mounting rail.