Technical specifications
16.1 Standards, approvals and safety instructions
Automation system
System Manual, 01/2023, A5E03461182-AK
341
FM approval
Factory Mutual Research (FM) according to
Approval Standard Class Number 3611, 3600, 3810
ANSI/UL 121201
ANSI/UL 61010-1
CAN/CSA C22.2 No. 213
CAN/CSA C22.2 No. 61010-1
CAN/CSA C22.2 No. 0-10
APPROVED for use in Class I, Division 2, Group A, B, C, D T4;
Class I, Zone 2, Group IIC T4
Installation Instructions for FM
WARNING - Explosion Hazard - Do not disconnect while circuit is live unless area is known
to be non-hazardous.
WARNING - Explosion Hazard - Substitution of components may impair suitability for Class
I, Division 2 or Zone 2.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D; Class I, Zone 2,
Group IIC; or non-hazardous locations.
These products need to be connected by means of the front connector Cat. No. 6ES7592-
1AM00-0XB0
WARNING: EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF
MATERIALS USED IN THE RELAYS.
ATEX approval
According to EN 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part
15: Type of protection "n") and EN IEC 60079-0 (Electrical apparatus for potentially explosive
gas atmospheres - Part 0: General requirements).
II 3 G Ex nA IIC T4 Gc
DEKRA 12ATEX0004 X
OR
According to EN IEC 60079-7 (Electrical apparatus for potentially explosive atmospheres - Part
7: Increased safety "e") and EN IEC 60079-0 (Electrical apparatus for potentially explosive gas
atmospheres - Part 0: General requirements).
II 3 G Ex ec IIC T4 Gc
DEKRA 20ATEX0003 X