Technical specifications
16.1 Standards, approvals and safety instructions
Automation system
344 System Manual, 01/2023, A5E03461182-AK
OR
According to IEC 60079-7 (Explosive atmospheres - Part 7: Equipment protection by increased
safety "e") and IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General
requirements).
II 3 G Ex ec IIC T4 Gc
IECEx DEK 21.0028 X
Special conditions in hazardous areas:
The equipment shall only be used in an area of not more than pollution degree 2, as
defined in IEC 60664-1.
The device must be installed in a suitable housing that ensures at least IP54 degree of
protection according to IEC 60079-0. The ambient conditions must be taken into
consideration for use.
Provisions shall be made to prevent the nominal voltage from being exceeded by transient
disturbances of more than 119 V.
CCCEx approval
According to GB/T 3836.3 (Explosive atmospheres - Part 83: Equipment protection by type of
protection "e"), GB/T 3836.1 (Explosive atmospheres - Part 1: Equipment - General
requirements).
Ex ec IIC T4 Gc
Special conditions in hazardous areas:
The equipment shall only be used in an area of not more than degree of pollution 2, as
defined in GB/T 16935.1.
The equipment shall be installed in a suitable enclosure providing a degree of protection
not less than IP54 in accordance with GB/T 3836.1. The ambient conditions must be taken
into consideration for use.
Provisions shall be made to prevent the nominal voltage from being exceeded by transient
disturbances of more than 119 V.
RCM Declaration of conformity for Australia/New Zealand
The S7-1500 automation system/ET 200MP distributed I/O system fulfills the requirements of
the standard IEC 61000-6-4.
Korea Certification
Please note that this device corresponds to limit value class A in terms of the emission of
radio frequency interference. This device can be used in all areas, except residential areas.
기기는 업무용(A) 전자파 적합기기로서 판매자 또는 사용자는 점을 의하시기 바라