Technical specifications
16.1 Standards, approvals and safety instructions
Automation system
System Manual, 01/2023, A5E03461182-AK
343
UKEX approval
According to EN IEC 60079-7 (Explosive atmospheres Part 7: Equipment protection by
increased safety "e") and EN IEC 60079-0 (Explosive atmospheres - Part 0: Equipment -
General requirements).
II 3 G Ex ec IIC T4 Gc
DEKRA 21UKEX0008 X
T-CPUs:
According to EN IEC 60079-7 (Explosive atmospheres - Part 7: Equipment protection by
increased safety "e") and EN IEC 60079-0 (Explosive atmospheres - Part 0: Equipment -
General requirements).
II 3 G Ex ecnA IIC T4 Gc
DEKRA 21UKEX0007 X
Special conditions in explosive atmospheres:
The equipment shall only be used in an area of not more than degree of pollution 2, as
defined in EN 60664-1.
The equipment shall be installed in a suitable enclosure providing a degree of protection
not less than IP54 in accordance with EN IEC 60079-0. The ambient conditions must be
taken into consideration for use.
Provisions shall be made to prevent the rated voltage from being exceeded by transient
disturbances of more than 119 V.
IECEx approval
According to IEC 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n") and IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General
requirements).
II 3 G Ex nA IIC T4 Gc
IECEx DEK 13.0010 X
OR
According to IEC 60079-7 (Explosive atmospheres - Part 7: Equipment protection by increased
safety "e") and IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General
requirements).
II 3 G Ex ec IIC T4 Gc
IECEx DEK 19.0087 X
T-CPUs
According to IEC 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n") and IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General
requirements).
II 3 G Ex nA IIC T4 Gc
IECEx DEK 16.0045 X