Technical specifications
A.3 Fail-Safe signal module (SM) technical specifications
S7-1200 Functional Safety Manual
Manual, 02/2015, A5E03470344-AA
173
Model
SM 1226 F-DI 16 x 24 VDC
Module fault display
Red / Green LED (DIAG)
Diagnostic information can be displayed Possible (TIA Portal, HMI, or Web page)
Table A- 47 Performance
Model
SM 1226 F-DI 16 x 24 VDC
Tmax_i: Internal cycle time TBD
Note: Refer to Fail-Safe signal module (SM) response times"
(Page 197) for further information.
Table A- 48 Power supply (L+, M)
Model
SM 1226 F-DI 16 x 24 VDC
Voltage range
20.4 VDC to 28.8 VDC
Surge voltage
35 VDC for 0.5 s
Input current
130 mA with no current out of Vs1 and Vs2
730 mA with maximum current out of Vs1 and Vs2
Hold up time (loss of power)
1.0 ms at 20.4 VDC
Internal fuse, not user replaceable
2.5 A
Reverse polarity protection
Yes
Table A- 49 Sensor power (Vs1 / Vs2)
Model
SM 1226 F-DI 16 x 24 VDC
Number of outputs
2
Voltage range
L+ minus 2.0 VDC minimum
Output current rating (maximum)
300 mA
Permissible total current of outputs
600 mA
Short-circuit protection:
Operating value
Yes
0.7 A to 2.1 A