Data Exchange with the Central Controller
4–51
IP244
C79000–B8576–C860–02
Byte 28 Main control byte 2
OFF
ON
Yes
No
Read channel 13 +
Error processing
In °F
In °C
Bit3210 Thermocouple type
0000 FeĆconstantanĆthermocouple type L
to DIN 43710
0001 FeĆconstantanĆthermocouple type L
to DIN 43710
0010 NiCrĆNiĆthermocouple, type K to IEC 584
0011 Pt10% RhĆPtĆthermocouple type S to IEC 584
0100 FeĆconstantanĆthermocouple type J to IEC 584
0101 Pt100 to DIN 43760 *
)
0110 Pt13% RhĆPtĆthermocouple type R to IEC 584
All other codings are not used and must not
be selected.
Value of the
control bits 2
n
Logical
state
Required function
1
0
1
0
1
0
1
0
1
0
1
0
1
0
Temperature
value
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
Read channel 13 +
Error processing
*
)
In Pt 100 operation, only channels 0 to 7 are processed. Selection of heating
current monitoring, hot channel control and the special function is no longer
possible. The comparator can no longer be used (irrelevant in variant Ć3AB31).
1
0
Parameter monitoring
Yes
No
Not possible with hot
channel control,
heating current
monitoring or with pure
Pt 100 operation
Bit 7: This function applies for all controllers, for which self-tuning is possible (even if it
is not activated), when main control byte 1, bit 2 = ”1” and for all controllers where
a self-tuning function was run successfully, when main control byte 1, bit 2 = ”0”.
Bit 7 can be transferred to the IP with the FB 162 commands ”KS”, ”PA” or ”AE
message 15”:
If bit 7 = 1, bit 1 of the error bytes 0a to 12a is not set.