STAR
TUP / TROUBLESHOOTING
5-3
Hardware
and Installation User Manual
6. Using
the programming device, enter the I/O configuration.
7. Enter the RLL program. See the SIMATIC TI505 Programming
Reference
manual for information about designing your RLL program.
8. Use the programming device to JOG motors, solenoids, or other
positioning devices one at a time to establish correct rotation or
position.
After
all the steps are performed and verified, place the
PLC in the RUN mode.
If you turn ON the L-memory MEMORY PROTECT dipswitch, your RLL
program cannot be changed by a programming device that is connected to the
PLC
through one of the communication ports.
NOTE
The MEMORY PROTECT dipswitch does not prevent forcing
I/O, changing variable memory, or switching the PLC from
PROGRAM to RUN mode. These actions may be made by a
programming
device connected to the PLC, or a special function
I/O
module
designed for this type of interface to the PLC, e.g., a
Network Interface Module. The RLL can also be changed
through a special function module, even when the memory
protection
is enabled.
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.comArtisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TI525 and is the answer not in the manual?

Siemens SIMATIC TI525 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TI525
CategoryControl Unit
LanguageEnglish

Related product manuals