Description of system components   
8.6 Decoupling module (DCM) for 1st generation current/voltage measuring modules (e.g. 3UF711.1AA000) 
  SIMOCODE pro 
144  System Manual, 05/2019, A5E40507475002A/RS-AD/004 
The tables below show decoupling module requirements for different grounding systems and 
system configurations (star systems, delta systems, and single-phase systems): 
Star networks:  
Table 8- 1  Decoupling module requirements for star networks 
Decoupling module 
required? 
4-wire, star, grounded with 
low impedance 
No  "TN-S system" according to 
IEC 60364 
4-wire, star, grounded with 
high impedance 
Yes  — 
3-wire, star, grounded with 
low impedance 
No  "TN-C system" according to 
IEC 60364 
3-wire, star, grounded with 
high impedance 
Yes  — 
3-wire, star, with isolated 
neutral 
Yes  "IT system" according to 
IEC 60364