Description of system components 
  8.6 Decoupling module (DCM) for 1st generation current/voltage measuring modules (e.g. 3UF711.1AA000) 
SIMOCODE pro 
System Manual, 05/2019, A5E40507475002A/RS-AD/004 
145 
Delta configurations  
Table 8- 2  Decoupling module requirements for delta networks 
Decoupling module 
required? 
3-wire, delta, one phase 
grounded 
Yes  Parameter "Voltage 
display → phase voltages" 
must be active. 
3-wire, delta, 
with isolated ground 
Yes  Parameter "Voltage 
display → phase voltages" 
must be active. 
Center tap grounded 
Yes  Parameter "Voltage 
display → phase voltages" 
must be active. 
1) Mainly encountered in North America 
 
Single-phase systems  
Table 8- 3  Decoupling module requirements for single-phase networks 
Decoupling module 
required? 
 
 
Yes 
Parameter "Voltage 
display → Phase voltages" 
must be active. The voltage 
applied is calculated from