Description of system components 
  8.14 Configuration information for SIMOCODE pro V when using an older basic unit 
SIMOCODE pro 
System Manual, 05/2019, A5E40507475002A/RS-AD/004 
157 
Table 8- 8  Maximum configuration with expansion modules when using an operator panel/operator panel with display, a 
2nd generation current/voltage measuring module and a SIMOCODE pro V-PB basic unit with a product 
version earlier than E15 / SIMOCODE pro V Modbus basic unit with product version E01 
SIMOCODE pro basic unit 
U
s
 = 24 V DC 
SIMOCODE pro basic unit 
U
s
 = 110-240 V AC/DC 
OP  Measur
DM-
DM  AM  TM  EM  DM-
DM  AM  TM  EM 
OP  U/I 
 1)
-  -  ✓  ✓  ✓  -  -  ✓  ✓  ✓ 
OPD  U/I 
1)
Max. 2 modules 
1)
 
1) Max. 1 AM, TM, EM module 
 
Note 
Decoupling module 
A decoupling module is not
 necessary for 2nd generation current/voltage measuring 
 
Configuration instructions for the use of fail-safe expansion modules 
In conjunction with DM-F Local and DM-F PROFIsafe fail-safe digital modules, the 
expansion modules can be used as follows: 
 
Number of expansion 
modules 
 
 
Note 
Restrictions for the SIMOCODE pro V device series 
The restrictions mentioned here apply to the SIMOCODE
 pro V High Performance device 
series with the following product versions:
 
  SIMOCODE pro V PB: Before E15 
  SIMOCODE pro V PN: Before E10 
  SIMOCODE pro V MR: Before E03 
Devices with the stated product versions or later can be used without restriction with an 
operator panel with display and 2nd
 generation current/voltage measuring modules.