Safety and commissioning information for Ex areas   
14.1 Motor protection functions (overload protection, thermistor protection) 
  SIMOCODE pro 
306  System Manual, 05/2019, A5E40507475002A/RS-AD/004 
 
Setting the "response" of the overload protection 
Set the response of the overload protection to "Trip"! 
Example of a tripping characteristic with 3UF710* current/voltage measuring modules and  
3UF711*-1AA00-0 1st generation current/voltage measuring modules 
Motor 500 V, 50 / 60 Hz, 110 kW, 156 A, temperature class T3, time T
E
 = 11 s, I
A
 / I
s
 = 5.5: 
 
Figure 14-1  Tripping conditions of the Ex e motor, selected: CLASS 10 when using a 3UF710* 
current measuring module 
The latest tripping characteristics for SIMOCODE pro can be found in the  
Industry Online Support (Tripping characteristics 3UF7 
(
https://support.industry.siemens.com/cs/search?search=3UF7&type=Characteristic&lc=en-
WW)).